Pipe Pressure Drop Calculator

Find the friction pressure drop and head loss in a pipe with the Darcy–Weisbach equation, from flow rate or velocity, bore, length, pipe material and fluid.

Inputs

Flow

Pipe

Fluid

Result

Results

Pressure drop in kilopascals

23.7125 kPa

f × (L ÷ D) × ρV² ÷ 2 = 0.0237551 × (100 m ÷ 0.05 m) × 499.105 Pa.

Pressure drop in bar

0.237125 bar

Pressure drop in psi

3.43921 psi

Pressure drop in pascals

23,712.5 Pa

Head loss

2.42234 m (7.94732 ft)

ΔP ÷ (ρ × g): the height of a column of this fluid that the friction uses up.

Straight-pipe loss per 100 m

23.7125 kPa (1.04827 psi per 100 ft)

Darcy friction factor (f)

0.0237551

From the Colebrook–White equation, using Re and the relative roughness. ε ÷ D = 0.045 mm ÷ 50 mm = 9 × 10⁻⁴.

Reynolds number (Re)

49,831

Turbulent flow. Water at 20 °C: 1.0034 cSt and 998.21 kg/m³.

Flow rate

1.9635 L/s (7.06858 m³/h, 31.122 US gpm)

Q = V × A, with A = π × D² ÷ 4 = 1.963 × 10⁻³ m².

How to use the pipe pressure drop calculator

Enter the flow, either as an average velocity in m/s or ft/s or as a flow rate in L/s, L/min, m³/h or US gallons per minute. Then enter the pipe's inner diameter and its length. Use the actual bore, not the nominal size: a 2 inch Schedule 40 steel pipe has a 2.067 inch bore.

Choose the pipe material, which sets the wall roughness, or choose Other and type a roughness in millimeters. If the line has elbows, valves or tees, add up their loss coefficients and enter the total as ΣK. Leave it at 0 for straight pipe.

Choose Water at 20 °C or Air at 20 °C and 1 atm, or choose Other fluid and enter its viscosity and density. Unlike the Reynolds number, the pressure drop always needs the density, even when the viscosity is kinematic.

The answer leads with the pressure drop in the unit you pick and lists the other units under it. Below that are the head loss, the loss per 100 m of straight pipe, the friction factor, the Reynolds number and the flow rate or velocity worked out from what you entered.

The Darcy–Weisbach equation and the friction factor

ΔP = f × (L ÷ D) × ρV² ÷ 2, where f is the Darcy friction factor, L the pipe length, D the inner diameter, ρ the density and V the average velocity. ρV² ÷ 2 is the dynamic pressure of the flow, so the equation says that every bore's length of pipe uses up f times the dynamic pressure. Divided by ρ × g, the same loss is a head: h = f × (L ÷ D) × V² ÷ 2g.

The friction factor depends on the Reynolds number. In laminar flow it is exactly 64 ÷ Re and the wall roughness plays no part. In turbulent flow it depends on Re and the relative roughness ε ÷ D, and the calculator finds it from the Colebrook–White equation: 1/√f = −2 log₁₀(ε ÷ 3.7D + 2.51 ÷ (Re √f)). f appears on both sides, so the calculator solves it by iteration until it stops changing. The Moody chart is a plot of the same equation.

Fittings add K × ρV² ÷ 2 each, where K is the fitting's loss coefficient. The calculator adds ΣK to f × L ÷ D before multiplying by the dynamic pressure.

Worked examples: water, a US pipe run, oil and air

Water at 20 °C flows at 1 m/s through 100 m of commercial steel pipe with a 50 mm bore. These are the calculator's starting values. The Reynolds number is 49,831 and ε ÷ D = 0.045 ÷ 50 = 0.0009, so Colebrook gives f = 0.0237551. The dynamic pressure is 998.21 × 1² ÷ 2 = 499.105 Pa and L ÷ D = 2,000, so ΔP = 0.0237551 × 2,000 × 499.105 = 23.7125 kPa, a head loss of 2.42234 m.

The material matters. The same flow in drawn copper or plastic tubing loses 20.9777 kPa, and in cast iron 32.443 kPa. Adding fittings with a total K of 5 to the steel line adds 2.49553 kPa, for 26.2081 kPa in all.

In US units, 100 US gallons per minute of water through a 2 inch Schedule 40 steel pipe (2.067 inch bore) moves at 9.56112 ft/s and loses 7.4472 psi per 100 ft. In PVC of the same bore the loss falls to 5.95978 psi.

A hydraulic oil of 46 cSt and 870 kg/m³ flowing at 2 m/s in a 20 mm line has a Reynolds number of 870, so the flow is laminar and f = 64 ÷ 870 = 0.0736. Over 10 m it loses 64.032 kPa, whatever the pipe is made of.

Air at 20 °C moving at 5 m/s through 30 m of 200 mm galvanized duct loses only 50.5407 Pa, because air is about 830 times less dense than water.

Pipe roughness and fitting loss coefficients

The material choices use these absolute roughness values for new, clean pipe. Each is on Moody's 1944 chart and within the range the Engineering ToolBox gives. Old pipe is rougher: rusted steel can reach several millimeters, which can double the friction factor.

  • Drawn copper, brass, glass, PVC and PE tubing: 0.0015 mm. At ordinary flows this pipe is close to hydraulically smooth.
  • Commercial steel or wrought iron: 0.045 mm.
  • Galvanized iron or steel: 0.15 mm.
  • Cast iron, new: 0.26 mm.
  • Concrete: 0.3 mm when smooth, up to about 3 mm when rough.
  • Typical loss coefficients, which vary between sources and fitting designs: a sharp-edged pipe entrance about 0.5, an exit into a tank 1.0, a fully open gate valve about 0.2, a 90° elbow from about 0.3 (flanged, long radius) to 1.5 (threaded), and a fully open globe valve about 10.

Limits of the calculation

Darcy–Weisbach is exact as an equation, so the answer depends on how well the inputs describe the real pipe:

  • It gives the friction loss only. A pipe that climbs also needs the pressure to lift the fluid, ρ × g × height: 9.79 kPa for each meter of rise with water.
  • It assumes an incompressible fluid. For gases it holds while the pressure drop is less than about 10% of the absolute pressure. Beyond that, split the line into shorter pieces or use a compressible-flow method.
  • Between Re 2,300 and 4,000 no friction formula is reliable. The calculator uses Colebrook there, which gives the higher turbulent value.
  • It is for full pipes and Newtonian fluids. Partly full drains, slurries and other non-Newtonian fluids need other methods.
  • Viscosity changes strongly with temperature, so use values at the fluid's actual temperature. Warm water at 40 °C gives a lower loss than water at 20 °C.

Sources

Frequently Asked Questions

How much does the pressure drop rise if I double the flow?
In turbulent flow, by about four times, since the loss grows with V². The friction factor falls a little as Re rises, so it is slightly less: doubling the starting example's 1 m/s to 2 m/s raises the loss from 23.7125 kPa to 87.2023 kPa, 3.68 times. In laminar flow the loss is proportional to the velocity, so it exactly doubles.
What is the difference between the Darcy and Fanning friction factors?
The Darcy factor is four times the Fanning factor. Civil and mechanical engineers, and the Moody chart, mostly use Darcy, which is the one in ΔP = f × (L ÷ D) × ρV² ÷ 2 and the one this calculator shows. Chemical engineers often use Fanning, with ΔP = 4f × (L ÷ D) × ρV² ÷ 2. In laminar flow Darcy is 64 ÷ Re and Fanning is 16 ÷ Re.
Should I use Darcy–Weisbach or Hazen–Williams?
Darcy–Weisbach works for any Newtonian fluid, any temperature and laminar or turbulent flow. Hazen–Williams is an empirical formula for water at ordinary temperatures in turbulent flow, popular in fire sprinkler and water supply design because it is easy to use by hand. For oil, air, hot or cold water, or small pipes, use Darcy–Weisbach.
How do I convert head loss to pressure?
Multiply by the fluid's density and by g: ΔP = ρ × g × h. For water at 20 °C, 1 m of head is 998.21 × 9.80665 = 9,789 Pa, or 9.79 kPa, and 1 ft of head is about 0.433 psi. The starting example's 2.42234 m of head is 23.7125 kPa.
What roughness should I use for old pipe?
Corrosion and scale make pipe rougher and narrower. The Engineering ToolBox gives 0.15 to 4 mm for rusted steel and 0.8 to 1.5 mm for worn cast iron. Choose Other, enter a roughness in that range and, if you know it, the reduced bore.